China Professional EV Charger solutions provider.

AC Wallbox, DC EV Charger, Pantograph charger.

info@dekon-china.com  whatsapp:0086-15356475680

Sales & Support
Request A Quote - Email
Select Language
English
Russian
Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home News

Six major benefits of EC motor when used in fan-coil units

Certification
Good quality AC wallbox charger for sales
Good quality AC wallbox charger for sales
when i see you first time, Simon, i believe we will have some business with you.And i like your water fan coil and your VRF air conditioner units.

—— Nassif-Lebanon

China Aire Acondicionado Piso Techo fabrica DEKON,Mejor equipos aires acondicionados en China.

—— JOSE

we have the request for water fan coil full range and DEKON made all these for us, and in CKD form, it is not easy to find such ono factory in China.

—— David

I'm Online Chat Now
Company News
Six major benefits of EC motor when used in fan-coil units
Six major benefits of EC motor when used in fan-coil units

Electronically commutated motors provide clear advantages over AC or conventional DC motors in terms of service life, controllability, flexibility, and cost-effectiveness explains CIVE PALFREY.

For the past 30 years, forward-bladed centrifugal fans in fan coil-units have been driven by AC motors, which are typically around 45% efficient. However, the latest electronically commutated (EC) motors are 80% efficient, leading to significant operational benefits.

Six major benefits of EC motor when used in fan-coil units

The term EC is applied to a DC motor having electronic commutation achieved with a microprocessor.

Commutation means applying a current to the motor phases to produce the best torque at the motor’s shaft. In brush-type motors, commutation is done electromechanically using graphite brushes and a commutator. In

 brushless motors, however, it is achieved by switching electronics using rotor-position information obtained by sensors.

Thus, the EC motor is essentially a DC motor that can be connected direct to an AC mains supply.

The EC motor used in Trox fan-coil units, for example, comprises an external-rotor motor having a permanent magnet with integrated electronics. It works in the same way as a brushless

 DC motor..

EC motor technology has been proved in many applications during the last five years. However, its application

 in fan coils is relatively novel.

Higher efficiency

The major advantage of EC motors over their AC counterparts is far higher efficiency, which enables a fan-coil unit to achieve a specific fan power (SFP) of 0.3 compared with 0.8 for an AC motor (the limit in the latest 

Building Regulations is 0.8 W/l/s).

This higher efficiency can be maintained at low speeds, so less motor heat is absorbed by the cold air 

discharged from the FCU, which in turn leads to more cooling applied in the space. Lower temperatures

 increase motor life, and in-built soft starting gives longer bearing life.

Speed control is simple, and results in impressive energy saving performance. The maximum cooling load

 on an FCU may only apply for 500 h out of a total annual running time of 3,000 h. With a typical fan coil unit, 

the fans deliver more air than necessary for 2500 h/year — a shocking waste of energy.

By using the temperature controller on an FCU to reduce the speed of the EC motor during periods of reduced 

cooling demand, you can cut energy wastage dramatically. For example, an annual fan energy consumption of 

620 kWh can be reduced to 140 kWh using speed control.

The reduction of air volume is, however, limited by considerations of the room air distribution. That is why we 

recommend that tests are undertaken in a suitable test facility to determine the optimum range of air volume.

Optimised

By using ceiling diffusers with suitable volume turndown characteristics, the air movement in the space can be 

optimised to ensure comfortable conditions throughout the turndown range.

Our tests indicate that a lower volume of 70% is possible, which results in the fan power being reduced by 50%. 

There is also less room noise as a result of the lower air volumes handled.

The pressure generated by an FCU is directly related to the amount of energy consumed. By reducing the external 

pressure-drop in a system and the internal losses of the FCUs, it will be possible in the future to ensure that such systems 

meet lower energy limits when combined with high-efficiency motors. For example, the stepless volume control possible with EC motors many make balancing dampers 

in the downstream ductwork unnecessary.

Energy saving

The availability of EC motor technology will enable FCU manufacturers to work with motor manufacturers to develop

 further energy-saving solutions, particularly important in today’s environmentally-conscious world.

Six major benefits of EC motor when used in fan-coil units

Electronically commutated motors offer six major benefits when used in fan-coil units.

• High efficiency of 85%, leading to lower input power.
• Lower rise in air temperature on the air stream.
• Efficient speed control.
• Longer motor life resulting from lower running temperatures.
• Longer bearing life because of the soft-start feature.
• Suitable for a 230 V supply.